PSS 21H-1B2 B3
Page 6
SPECTRUM Migration Interfacing
The Control Processor 30 interfaces with a
SPECTRUM Migration Integrator subsystem via a
single or redundant I/A Series Fieldbus and a
Fieldbus Processor (FBP) with built-in FBP isolator
located within the subsystem. There are four different
FBP integrators to accommodate Unit Control
Modules (UCM), Field Input/Output Units (FIO),
Universal Field Multiplexers (UFM), and Universal
Input/Output Units (UIO).
The CP30 control strategy can include any of
following SPECTRUM configurations:
• a single SPECTRUM Migration Integrator
subsystem
• multiple types of SPECTRUM Migration
Integrator subsystems
• Fieldbus Modules (FBMs) and/or other Fieldbus-
based process interface subsystems along with
the SPECTRUM Integrator subsystem(s)
Control is via the software resident in the FBP
Integrator and in the SPECTRUM I/O Equipment
Control Blocks (ECBs) operating at the CP level.
Figure 7 illustrates a typical configuration with
multiple types of Integrator subsystems with nests of
I/O cards. (Refer to PSS 21H-7Q1 B3 SPECTRUM
Migration Integrators for additional information.)
Figure 7. Twinaxial Fieldbus SPECTRUM Migration Subsystem Interface Configuration (Typical Configuration)
CONTROL
PROCESSOR
30**
FBP11
INTEGRATOR*
TCA
TCA
TO/FROM
PROCESS DEVICE(S)
TERMINATING
RESISTOR
FIELDBUS*
ABBREVATIONS:
TCA = Termination Cable Assembly
I/O = Input/Output
FBP = Fieldbus Processor
* OPTIONALLY REDUNDANT
** OPTIONALLY FAULT-TOLERANT
I/O
CARD
1
I/O
CARD
N
N = UP TO 30 CARDS
TERMINATING
RESISTOR
TCA
NOTE: FBP INTEGRATORS HAVE BUILT-IN FIELDBUS ISOLATORS.
UCM RACK
FBP12
INTEGRATOR*
TCA
TO/FROM
PROCESS DEVICE(S)
I/O
CARD
1
I/O
CARD
N
N = UP TO 128 CARDS
FIO RACK
FBP13
INTEGRATOR*
TCA
TO/FROM
PROCESS DEVICE(S)
I/O
CARD
1
I/O
CARD
N
N = UP TO 96 CARDS
UFM RACK
FBP14
INTEGRATOR*
TO/FROM
PROCESS DEVICE(S)
I/O
CARD
1
I/O
CARD
N
N = UP TO 30 CARDS
UIO RACK