PSS 21H-1B2 B3
Page 7
SPEC 200 Control Interfacing
For migration of SPEC 200 control to I/A Series
systems, the Control Processor 30 interfaces via a
single or redundant I/A Series Fieldbus with the
SPEC 200 Control Integrator subsystem. This
subsystem consists of individual Control Integrators,
and Fieldbus Isolators attached within the SPEC 200
rack.
Control is via the software resident in the Control
Integrator and in the SPEC 200 I/O Equipment
Control Blocks (ECBs) operating at the CP level.
Figure 8 illustrates a typical configuration with
multiple Control Integrators in the SPEC 200
subsystem. (Refer to PSS 21H-7R1 B3 SPEC 200
Control Integrators for additional information.)
Figure 8.
Twinaxial Fieldbus SPEC 200 Control Subsystem Interface Configuration (Typical Configuration)
CONTROL
PROCESSOR
30**
SSFBI*
TCA
TO/FROM
PROCESS DEVICE(S)
TERMINATING
RESISTOR
FIELDBUS*
ABBREVATIONS:
TCA = Termination Cable Assembly
SSFBI = SPEC 200 Single Fieldbus Isolator
* OPTIONALLY REDUNDANT
** OPTIONALLY FAULT-TOLERANT
N = UP TO 24 CARDS
CONTROL
INTEGRATOR N
CONTROL
INTEGRATOR 1
SPEC 200
RACK 1
SSFBI*
TO/FROM
PROCESS DEVICE(S)
N = UP TO 24 CARDS
CONTROL
INTEGRATOR N
CONTROL
INTEGRATOR 1
SPEC 200
RACK 2
TERMINATING
RESISTOR
Comentarios a estos manuales